When installing the STAHL 261384 Transmitter Supply Unit in a potentially explosive area (zone 2), it is important to follow the specified conditions and safety guidelines. Here are the installation instructions:
1. Install the device in a suitable, approved housing that meets the requirements of IEC/EN 60079-15 and has at least IP54 protection.
2. Observe the requirements of IEC/EN 60079-14.
3. Only connect or disconnect cables and adjust the DIP switch when the power is disconnected in zone 2.
4. If the device is damaged, subject to an impermissible load, stored incorrectly, or malfunctions, it must be stopped and immediately removed from the Ex area.
It is crucial to consult the complete instruction manual for detailed installation instructions and safety precautions.