Answer

Apr 12, 2025 - 04:44 AM
The allows for the control of up to six heaters. This includes one control unit and up to five additional non-control units. However, please note that the number of non-control units permitted may vary depending on the unit size. For example, unit size 400 can have five additional non-control units, unit size 800 can have three additional non-control units, and unit size 1200 can have two additional non-control units. It is important to refer to Table 1 in the installation guide to determine the specific number of non-control units permitted for your model and voltage.