Answer
Apr 11, 2025 - 10:29 AM
To install the ENCELIUM High Bay Sensor into the DALI High-Bay Adapter, follow these steps:
1. Remove the High-Bay Sensor cover by turning it counterclockwise and place it aside.
2. If you are installing the High-Bay Sensor into the DALI High-Bay Adapter, remove the cover plate by turning it counterclockwise and lifting it up. The included cover plate is not needed when the High-Bay Sensor is mounted into the DALI High-Bay Adapter.
3. Cut a Ø 22 mm (0.87 inch) hole in the ceiling.
4. Line up the DALI High-Bay Adapter holes to the ceiling hole and xxxx it into the ceiling.
5. Connect the Mains and DALI wires into the DALI High-Bay Adapter connector block.
6. Connect the High-Bay Sensor wires into the DALI High-Bay Adapter connector block.
7. Place the High-Bay Sensor into the DALI High-Bay Adapter and push it until it clicks into place.
8. Install the High-Bay Sensor cover by turning it clockwise until it is secure.
For more detailed instructions and illustrations, please refer to the ENCELIUM High Bay Sensor Instruction Manual.