To connect the access controller to various devices, you will need to follow the wiring instructions provided in the user guide. Here is a summary of the wiring connections:
1. Power Supply - Access Controller: Use RVV2*1.0 wire with a distance of less than 100 meters.
2. Access Controller - Reader: Use RVV4*0.5 wire with a distance of up to 60 meters (maximum 100 meters).
3. Access Controller - Electric Lock: Use RVV4*1.0 wire with a distance of less than 150 meters.
4. Access Controller - Exit Button: Use RVV2*0.5 wire with a distance of less than 200 meters.
5. Access Controller - IR Alarm: Use RVV2*1.0 wire with a distance of less than 200 meters.
6. Access Controller - Sound-light Alarm: Use RVV2*1.0 wire with a distance of less than 150 meters.
7. RS485 Communication Cable: Use RVVP2*1.0 wire with a distance of less than 1000 meters. Connect the shield layer to ground.
8. TCP/IP Communication Cable: Use CAT-5 cable with a distance of less than 100 meters.
Please refer to the user guide for more detailed wiring diagrams and instructions.
Note: It is important to follow the wiring instructions carefully and ensure proper power supply and grounding to avoid any issues with the access control system.