Answer

Apr 09, 2025 - 11:33 AM
To install the TRANE BAYSPEK060 Single Point Entry Kit, follow these steps:
1. Check for any shipping damage and report it to the carrier immediately.
2. Verify that the available power supply complies with the requirements of the single power entry kit, heater, and unit model being used.
3. Remove the Control/Heat panel.
4. Open the louvered Heater Control box door and mount the SPEK inside the Heater Control box using the screws provided in the kit.
5. Insert the included grommet in the hole in the Heater Control box base that leads to the unit Control/Heater compartment. The unit power wires provided with the SPEK will pass through this grommet and be routed up to the unit contactor.
6. Make all electrical connections to the unit and heater according to the appropriate wiring diagram included with the specific SPEK.
7. Place the included SPEK wiring diagram on the inner surface of the Control/Heater access panel next to the unit wiring diagram and extra heater wiring diagram.
8. Attach the two nameplate labels included with the single power entry kit to the air conditioning unit or heat pump unit. The smaller label should be placed over the unit rating nameplate to cover the unit only MCA and Fusing.
9. Check the appropriate kit, heaters, and unit combination using the tables provided in the installation guide.
10. For high voltage field wiring, ensure that the field wire is rated 75°C minimum and the maximum field wire size is 2/0 AWG. Install the proper size fuses per the fuse table and ampacity and max fuse/circuit breaker tables for the specific SPEK being used. Route the field wires through the unit heater section and connect the power supply to the terminal block or fuse block on the SPEK. Connect the power supply ground wire to the ground lug on the single power entry kit.
11. Close the Heater/SPEK control box cover.
12. Reinstall the Control/Heat access panel.
13. Apply power to the unit.
14. For low voltage wiring (24 Volts), all lower voltage connections have been made to the heater via polarized plugs. The low voltage controls are connected to the room thermostat from the air conditioner or heat pump low voltage leads. Refer to the field wiring diagram provided with the unit.
Please note that these instructions are a summary and it is important to refer to the complete TRANE BAYSPEK060 Single Point Entry Kit Installation Guide for detailed and specific instructions.