To install the , please follow the instructions below:
1. Ensure that you have a certified electrician to install the motor interface according to the current electrical regulations.
2. Before installation, disconnect the motor interface from the mains supply to prevent unintentional connections.
3. The motor interface should be fitted into the window profile next to the WindowMaster operators.
4. Connect the WindowMaster operator to the motor interface using the double pole plug.
5. Connect the 2-meter long 3-core cable to the mains supply through a switch for control.
6. The primary mains supply should be 230V AC, 50/60 Hz, with a power consumption of 50 VA.
7. The motor interface provides a nominal output voltage of ±24 V DC, with a maximum current of 0.8 A. The operating time should not exceed 2 minutes per 5 minutes (40% duty cycle).
8. The motor interface has an IP value of IP 44, indicating its resistance to dust and water.
9. The dimensions of the motor interface are 160 x 29 x 42 mm (W x H x D).
Please note that these instructions are a summary and it is important to refer to the complete installation instructions provided in the manual for detailed guidance.