To select the module address for the QMC1 Communication Extension Module, follow these steps:
1. Locate the module address selection rotary switch on the base part of the module.
2. Use a small flat blade screwdriver to select the module address. The module address differs depending on the model name.
3. For the QMC1-0 [Console selection (MODBUS RTU/SIF)], the module address is obtained by adding 1 to the value of the selected rotary switch. The module address ranges from 0 to F (1 to 16).
4. For the QMC1-1 (C series compatible), the module address is the same as the value of the selected rotary switch. The module address ranges from 0 to F (0 to 15).
Make sure to select the appropriate module address to ensure proper communication with the host computer or PLC.