The battery runtimes for the Schneider Electric Easy UPS 3M are listed in minutes and vary depending on the load level and UPS rating. The runtimes provided are estimated values based on battery manufacturer data for operation at 25 °C. It is important to note that the runtimes mentioned are specific to certain battery types and may not apply to previous versions of the UPS models.
To provide a complete answer, I will provide a summary of the battery runtimes for different load levels and UPS ratings as mentioned in the user manual:
Battery Runtimes for 60 and 80 kVA UPSs and Classic Battery Cabinets:
- E3MCBC7C:
- 25% load: 40.5 minutes
- 50% load: 17 minutes
- 75% load: 9.6 minutes
- 100% load: 6 minutes
- E3MCBC7D:
- 25% load: 64 minutes
- 50% load: 28 minutes
- 75% load: 16.5 minutes
- 100% load: 11 minutes
- E3MCBC10A:
- 25% load: 100 minutes
- 50% load: 44.5 minutes
- 75% load: 26.5 minutes
- 100% load: 18 minutes
- E3MCBC10B:
- 25% load: 120 minutes
- 50% load: 54 minutes
- 75% load: 32.5 minutes
- 100% load: 22 minutes
- E3MCBC10C:
- 25% load: 135 minutes
- 50% load: 61 minutes
- 75% load: 37 minutes
- 100% load: 25.5 minutes
- E3MCBC10D:
- 25% load: 225 minutes
- 50% load: 100 minutes
- 75% load: 63 minutes
- 100% load: 44 minutes
- E3MCBC10E:
- 25% load: 270 minutes
- 50% load: 120 minutes
- 75% load: 76 minutes
- 100% load: 53.5 minutes
- 2 x E3MCBC7C:
- 25% load: 92.5 minutes
- 50% load: 40.5 minutes
- 75% load: 24.5 minutes
- 100% load: 16.5 minutes
- 2 x E3MCBC7D:
- 25% load: 140 minutes
- 50% load: 64 minutes
- 75% load: 39 minutes
- 100% load: 27 minutes
These are just a few examples of the battery runtimes provided in the user manual. For more specific information on different UPS ratings and load levels, please refer to the complete table in the user manual or contact Schneider Electric for confirmation.