Answer

Mar 06, 2025 - 12:10 AM
To reset the URC AC-PRO-II trip unit, you can use the "Force Reset" function. This function is located in register 83 and is an output coil (write only). To reset the trip unit, write a value of 1 to register 83. This will reset the trip unit and clear any active alarms or trip events. Please refer to the AC-PRO-II Instruction Manual for more detailed instructions and information on using the Modbus registers.