Answer

Mar 04, 2025 - 11:35 PM
Sure! Here are the step-by-step instructions for installing the INTERMATIC ET2725CR Electronic 2-Circuit 7-Day Time Switch:
1. Disconnect power: Before installing or servicing the time switch, make sure to disconnect power at the circuit breaker(s) or disconnect switch(es).
2. Bonding: For plastic enclosures, bonding between conduit connections is not automatic and must be provided as part of the installation.
3. Wiring: Use #14-#8 AWG wires, rated at least 105°C - COPPER conductors ONLY. Strip 1/2 inch off the supply and load wires. Torque the wires to 15.6 lbf-in.
4. Mounting: Choose a suitable location for the time switch enclosure and securely mount it using the provided mounting holes.
5. Connect wires: Connect the wires to the proper terminals on the time switch and tighten the screws firmly. Refer to the wiring diagrams in the manual for guidance.
6. Grounding: Connect the ground wire to the grounding terminal at the bottom of metal enclosures.
7. Insulator: Make sure there is no wire insulation under the terminal plate on the time switch connector. Return the insulator to its original position and replace the xxxx .
8. Close enclosure: Close the time switch enclosure door and make sure it is securely closed at all times when not servicing.
9. Apply power: Finally, apply power to the time switch and it will be ready for use.
Please note that these are general installation instructions. It is important to follow the specific instructions provided in the INTERMATIC ET2725CR Electronic 2-Circuit 7-Day Time Switch Instruction Manual for your safety and to ensure proper installation.