To install the APsystems 2300532 25A AC Connector EN 3-Wire, follow these steps:
Step 1: Verify the AC connector type. Make sure you have the correct connector, either the 25A AC Male Connector (EN,3-wire) or the 25A AC Female Connector (EN,3-wire).
Step 2: Prepare the wires. Strip the insulation from the wires using a wire stripper. The recommended wire gauge is 3x2.5mm²~4mm² (or 14AWG~12AWG), and the cable outer diameter should be between 10mm and 12mm. The earth wire should be longer than the live and neutral wires.
Step 3: Install the AC connectors. Set the parts on the cable in the order of 1→2→3→4. Crimp the wires according to the printed markings on the plastic core of the connector. Use a xxxx twisting torque of 0.8 +/_0.1N.m. Push the housing into the body until you hear a click sound. Insert the seal and clamp finger into the body, then tighten the nut to the specified torque.
Note: The installation process for the cable end female connector is the same as the male connector.
If the microinverter's output is L,N,PE (Line, Neutral, Protective Earth), the wiring method should be as follows:
Connector Power Grid
L L
N N
PE PE
If the microinverter's output is L,L,N (Line, Line, Neutral), the wiring method should be as follows:
Connector Power Grid
L L
N L
PE N
For any further assistance or clarification, you can contact APsystems at 844-666-7035 or visit their website at apsystems.com.