Answer

Mar 01, 2025 - 06:40 AM
To enable the function of reporting to the cloud for your Coolmay PLC, you can follow these steps:
1. Set the PLC IP address:
- Automatic acquisition: The M8324 register is set when the M8002 is powered on.
- Manual settings:
- Method 1: Write directly to the IP register.
- Gateway address: R23800 R23801; default 192.168.1.1. Set R23800=0XC0A8 and R23801=0X0101.
- Subnet mask: R23802 R23803; default 0.0.0.0. Set R23802=0 and R23803=0.
- IP address: R23807 R23808; default 192.168.1.250. Set R23807=0XC0A8 and R23808=0X01FA.
- Method 2: Use the cloud parameter setting software (Cloudset.exe) to set.
2. Set cloud parameters:
- SET M8326 in the ladder program enables the function of reporting to the cloud.
By following these steps, you should be able to enable the function of reporting to the cloud for your Coolmay PLC.