To install the Knightsbridge TPB14EMSLED LED Bulkhead Light, please follow these steps:
1. Ensure that you have read and understood the general instructions provided in the manual, and that you have the necessary knowledge and qualifications to carry out the installation safely.
2. Before starting the installation, isolate the mains power to the area where the light will be installed.
3. Check the total load on the circuit to ensure it does not exceed the rating of the circuit cable, fuse, or circuit breaker.
4. Take note of the IP (Ingress Protection) rating of the product to determine the suitable location for installation.
5. The TPB14EMSLED LED Bulkhead Light is Class II double insulated and IP44 rated.
6. Provide power to the required point of installation following the correct cabling methods outlined in BS7671 (IEE Wiring Regulations).
7. Use suitable IP rated junction boxes where required.
8. Remove the diffuser by rotating the bezel anti-clockwise.
9. Loosen the three LED plate screws.
10. Remove the LED plate and disconnect it from the driver and emergency inverter via the DC sockets.
11. Drill the fixing holes in the rear of the fitting, ensuring not to interfere with any gas/water pipes or electrical cables.
12. Feed the mains cable through the rubber grommet to retain the IP rating, and secure the baseplate to the surface.
13. Connect the luminaire to the mains supply, ensuring the correct polarity is observed (L- Permanent Live, K- Switched Live (brown), N- Neutral (blue)).
14. The additional terminal called Slave Live (SL) is available to enable the sensor to power on additional luminaires. A maximum of 500W LED load can be controlled by the sensor.
15. Reconnect the LED plate to the driver and inverter via the DC sockets.
16. Connect the battery to the socket on the emergency inverter.
17. Refasten the three LED plate screws.
18. Reattach the diffuser by rotating it clockwise.
19. Switch on the power and check for correct operation, ensuring the green indicator LED is illuminated.
20. It is recommended to charge the installation for a minimum of 24 hours before carrying out an emergency duration test.
21. If the batteries have been left in a discharged state for an extended period, it is recommended to complete one or more charge and discharge cycles to restore battery capacity.
Please note that these are general installation instructions, and it is important to refer to the specific manual provided with the product for detailed instructions and any additional information.