Answer

Feb 26, 2025 - 08:28 PM
To install the Danfoss KP 1W Pressure Switch, please follow the steps below:
1. Before starting the installation, make sure to disconnect the power supply to avoid electrical shock or damage to the equipment.
2. Choose a suitable location for mounting the pressure switch. Ensure that the ambient temperature is within the specified range of -40 to 65 °C and the relative humidity is between 30 and 98%.
3. Mount the pressure switch securely, taking into account the vibrations resistance of 4 g (10 - 1000 Hz).
4. For KP 1W, KP 1 manual reset, and KP 5, KP 5A, KP 6, KP 6A, KP 7 models, make the necessary wiring connections. Use copper wire only and tighten the connections with a torque of 20 lb. in. Follow the wiring diagram provided in the manual.
5. For KP 1, KP 2, and KP 4 models, the contact 1-4 opens on pressure drop. The AC 1 contact is rated at 16 A, DC 13 contact is rated at 12 W, and AC 3 contact is rated at 16 A for 400 V AC. Use a 16 Amp fuse for short circuit protection.
6. For KP 1W and KP 1 manual reset models, the contact 1-2 opens on pressure rise. These models are listed as refrigeration controller 61B5 according to UL regulations.
7. Set the desired pressure settings using the adjustment mechanism provided on the pressure switch. Refer to the manual for specific instructions on adjusting the pressure settings.
8. After installation, it is recommended to regularly check the function of the pressure switch to ensure proper operation.
Please note that the above instructions are a general guide. For detailed and specific installation instructions, refer to the Danfoss KP 1W Pressure Switch Installation Guide provided by the manufacturer.
Add New Comment