Answer

Feb 26, 2025 - 06:14 AM
To properly install the with male threaded connections, please follow these steps:
1. Ensure that the end of the pipe is clean and accurately deburred using the Oventrop universal tool.
2. Choose the appropriate compression fitting with male threaded connection according to the corresponding drawing.
3. Carefully inspect the O-rings on the compression fitting to ensure they are not damaged or pushed out of the grooves.
4. Push the composition pipe completely onto the fitting, ensuring it is fully inserted.
5. Using the appropriate tool, tighten the collar nut or pressure xxxx . For pipe sizes 14, 16, 18, and 20 mm, tighten to approximately 40-50 Nm. For pipe sizes 26 and 32 mm, tighten to approximately 80-90 Nm.
6. It is important to note that the compression fittings should only be used once. Do not reuse them.
7. After installation, it is recommended to perform a leakage test following standard procedures to ensure a secure connection.
Please refer to the provided installation instructions for any additional details or modifications.