To install the WXHU Lindab Smoke Control Dampers, follow these steps:
1. Preparations:
- Cut the ducts at right angles.
- Remove any burrs from the cut edges to reduce the risk of damaging the gasket.
- Cut away any needles created from the fold.
2. Assembly:
- Start by inserting the turned-over edge of the damper into the duct.
- Ensure that the first lip of the gasket is in contact with the edge of the duct all the way around and sticks straight out without any twists.
- Push the end of the damper into the duct, twisting it slightly to aid insertion.
- Secure the damper in the duct using self-tapping screws with a diameter of Ø4.2mm and a length of 13mm.
- Position the fasteners close to the damper (minimum 10-15mm) to support its weight and prevent damage to the gasket.
- Note that the damper must be installed on a certified and CE marked smoke control system. Refer to the mounting instruction of the whole smoke control system for further guidance.
Please refer to the WXHU Lindab Smoke Control Dampers Installation Guide for more detailed instructions and illustrations.