Answer

Feb 25, 2025 - 08:11 PM
To install the TOSHIBA APG001Z TOSVERT VF-PS1 Series APOGEE FLN Option Unit, please follow these steps:
1. Before starting the installation, make sure to turn off the input power of the VF-PS1 inverter and wait for at least 15 minutes. Check that the CHARGE lamp on the VF-PS1 is no longer lit.
2. Use a flat-blade screwdriver to release the panel mounting tab on the front panel cover of the inverter. Insert the screwdriver into the two holes at the upper part of the front panel and push it down to release the tab. Remove the front panel cover.
3. Install the APG001Z option by fitting the tabs on the lower side of the option into the slots at the lower part of the inverter front panel. Make sure the option is securely attached to the inverter. Check that the plastic bosses on the inverter case have fitted into the holes at the upper and lower parts of the option.
4. Attach the front cover to the inverter by inserting the tabs at the lower part of the front cover into the slots at the lower part of the inverter.
5. Stick the enclosed "LED name label" in the option LED display part of the front cover.
Please note that these are general installation instructions. For more detailed information and illustrations, refer to the TOSHIBA APG001Z TOSVERT VF-PS1 Series APOGEE FLN Option Unit Instruction Manual. Make sure to follow all safety precautions and consult the manual for any specific requirements or recommendations for your installation.