Answer

Feb 24, 2025 - 07:46 AM
To connect the to your 24V lead-acid battery, follow these steps:
1. Locate the AC terminals labeled "L" and "N" on the charger. Connect these terminals to an AC voltage source of (100~277)V using a greater than BVR 1.0mm2 multi-strand copper line.
2. Find the CF terminals labeled "Charging Fail Alarm" on the charger. Internal connect these terminals to the B- terminal via the normal close contact of a relay with 1A capacity.
3. Connect the B- terminal of the charger to the negative terminal of your 24V lead-acid battery using a greater than BVR 2.0mm2 multi-strand copper line.
4. Connect the B+ terminal of the charger to the positive terminal of your 24V lead-acid battery using a greater than BVR 2.0mm2 multi-strand copper line.
Once the connections are made, the charger will start charging your battery. The charger has LED indicators to show the charging status. The green LED indicator labeled "FULL CHARGED" will light up when the battery is fully charged. The red LED indicator labeled "CHARGING" will light up during the charging process.
Please refer to the SmartGen BAC2405CF Battery Charger User Manual for more detailed information and safety precautions.