Answer

Feb 24, 2025 - 12:46 AM
To set the auto transfer and auto restore function on the SmartGen HAT520NC ATS Controller, follow these steps:
1. Press and hold the button for more than 3 seconds to enter the parameter setting mode. All LEDs will illuminate to indicate lamp test mode.
2. Continue pressing the button until all LEDs start flashing (once per 500ms) to enter the parameter setting status. Release the button.
3. Press the button to cycle through the available settings.
4. To set the auto transfer non-restore function, make sure the 1# power indicator and 1# close indicator are illuminated, while the 2# power indicator and 2# close indicator are extinguished.
5. To set the auto transfer auto restore function, make sure the 2# power indicator and 2# close indicator are illuminated, while the 1# power indicator and 1# close indicator are extinguished.
6. After making the desired selection, press the button to save the parameter value. All LEDs will flash rapidly 5 times (once per 200ms) to indicate that the setting has been saved.
7. The controller will return to normal testing mode and operate according to the set auto transfer function.
Please refer to the SmartGen HAT520NC ATS Controller User Manual for more detailed instructions and information on other parameter settings.
Add New Comment