Answer

Feb 23, 2025 - 08:15 PM
To install the ICM CONTROLS ICM530 Surge Protective Device, please follow the instructions provided in the user manual. Here is a step-by-step guide:
1. Before installing the device, make sure to turn off the power at the main service panel by removing the fuse or switching off the appropriate circuit breaker.
2. It is important to note that installation should only be done by a licensed electrician for Type 1 devices or a licensed HVAC technician for Type 2 devices.
3. Determine if you have a Wye or Delta configuration.
4. Verify your mains voltage and match it with the ICM530 ratings.
5. Remove the cover on the service disconnect or electrical panel.
6. Mount the ICM530 through the 3/4" conduit connection of the electrical panel.
7. Remove the retaining ring and washer on the ICM530.
8. Feed the wires into the electrical panel or service disconnect.
9. Re-secure the retaining ring and washer.
10. Route the white wire to the neutral lug and secure it.
For Type 1 installation:
- Route the three black wires to the appropriate L1, L2, L3 connections before the breaker panel, following the wiring diagram and local electrical codes.
For Type 2 installation:
- Route and connect the three black wires (L1, L2, and L3) to the individual breakers on the circuit breaker panel, following the wiring diagram and local electrical codes.
- In the Delta configuration, there will be a white wire that needs to be capped off.
11. Reinstall the cover on the service disconnect or electrical panel.
12. Restore power. The green LED on the ICM530 should be on, indicating full protection.
Please note that these instructions are a summary of the installation process. It is essential to refer to the complete user manual for detailed instructions and safety precautions.
Add New Comment