Answer

Feb 21, 2025 - 02:06 AM
To properly install the Honeywell GSS Series GSAA01A1B General Purpose Safety Switches, follow these steps:
1. Consult with local safety agencies and their requirements when designing a machine-control link, interface, and all control elements that affect safety.
2. Strictly adhere to all installation instructions provided in the instruction manual.
3. Mount the switch using four M5 or #10 screws. Torque the screws to 4.9 Nm to 5.9 Nm [43 in-lb to 52 in-lb].
4. Remove the screws on the cover plate.
5. Connect stranded wire (0.75 mm2 to 2.5 mm2, 18-14 AWG) or solid wire (0.75 mm2 to 1.5 mm2, 18-16 AWG) to the connector terminals. Use 90 °C wire when the ambient temperature is over 75 °C. Torque the switch terminal screws to 0.8 Nm to 1.0 Nm [7 in-lb to 9 in-lb].
6. Seal the conduit opening according to the instructions provided in PK 80112.
7. Reassemble the cover plate and torque the cover screws to 0.5 Nm [4.4 in-lb].
For more specific information on adjustments, head orientation, actuation direction, wiring configurations, travel distances, and specifications, refer to the corresponding pages in the instruction manual.
It is important to follow these installation instructions to ensure proper operation and to prevent any potential risks or hazards.