To disconnect the Eaton IL01301056E Air Circuit Breaker for maintenance or repair, follow these steps:
1. Always de-energize primary and secondary circuits if the circuit breaker cannot be removed to a safe work location.
2. For drawout circuit breakers, lever (rack) them out to the disconnect position.
3. Switch all circuit breakers to the OFF position and discharge the mechanism springs.
4. Ensure that devices cannot be accidentally restarted.
5. Verify isolation from the power supply.
6. Disconnect the equipment from the supply and earth and short-circuit it.
7. Cover or provide barriers to adjacent live parts.
It is important to strictly follow these steps for all procedures described in the instruction manual to prevent any potential risks of death, bodily injury, or property damage. Always refer to the instructions contained in the manual and on the product labels for proper usage and safety guidelines.