Answer

Feb 19, 2025 - 09:46 PM
When the batteries cannot be immediately installed, it is recommended to store them in a clean, cool, and dry area. It is important to note that during storage, the batteries may lose capacity through self-discharge. Higher temperatures can increase the rate of self-discharge and reduce the storage life. The manual provides a chart that shows the relationship between open-circuit voltage (OCV) and storage time at various temperatures. The maximum storage times before a refresh charge is required and recommended open circuit voltage audit intervals are also provided in the manual. It is advised to give the batteries a refresh charge when the OCV approaches the equivalent of 2.10 Volts per cell or when the maximum storage time is reached, whichever occurs first. The manual also provides instructions on how to perform a refresh charge.