Answer

Feb 15, 2025 - 06:06 AM
To set the delay time for the normal and abnormal power supply in the SmartGen HAT530NC ATS Controller, follow these steps:
1. Enter the parameter setting mode by pressing and holding the button for more than 3 seconds until all LEDs are illuminated.
2. Use the button to navigate to the desired parameter number.
3. Press the button to enter the setting status for the selected parameter.
4. Use the button to adjust the number to set the desired delay time.
5. Press the button to confirm and save the setting.
6. Repeat steps 2-5 for other parameters if needed.
7. To exit the parameter setting mode, press and hold the button for more than 3 seconds.
The default delay time for the normal and abnormal power supply is 5 seconds. The range for the delay time is 0-60 seconds. Adjust the delay time according to your specific requirements.
Please refer to the SmartGen HAT530NC ATS Controller User Manual for more detailed instructions and information on other parameters and settings.