Answer

Feb 15, 2025 - 01:49 AM
To calibrate the iQ6 Internal Blower system, follow these steps:
1. Ensure that all filters, light bulbs, and duct systems are installed before calibration.
2. Hold the calibration button on the blower for 3 seconds. The calibration button will light up and stay on for up to 13 minutes.
3. The blower will start and begin the calibration process.
4. After calibration is complete, one of two things will occur:
- The blower turns off and the calibration button light stays on, indicating a successful calibration. Press the button to turn off the LED.
- The blower turns off and the calibration button light blinks continuously, indicating that there is too much restriction in the ductwork preventing the blower from achieving the rated airflow. In this case, the blower is automatically set to maximum intensity.
5. If there are too many restrictions in your hood system, you have three options:
- Accept the airflow as is by pressing the calibration button. The blower system will be configured to the highest possible performance.
- Correct the duct restriction, clear the original calibration data, and repeat the calibration process.
- Clear the calibration data to reset the hood to the default factory setting and achieve standard high-pressure blower performance. To do this, hold the calibration button for 10 seconds until the light blinks 3 times to confirm the reset.
6. Repeat the calibration process from the beginning if necessary.
Please refer to the iQ6 Internal Blower Instruction Manual for more detailed instructions and illustrations.