To replace the Communicator Classic with the new Communicator, follow these steps:
1. Physical Differences:
- Note that the power and network connectors are not in the same place, and the configuration port is different.
- The new Communicator is slightly taller than the Communicator Classic.
2. Configuration Conversion:
- The configuration conversion is intended to convert custom protocols and get the new Communicator up and running quickly.
- Start by locating the configuration file used with the Communicator Classic that needs to be converted.
- In the built-in web interface of the new Communicator, go to the Files & Firmware page and click the Import Anybus Communicator Classic configuration button.
- In the Import configuration window, select the configuration file (.cfg) and click Import.
- The configuration will be imported into the web interface of the new Communicator. A pop-up window may appear with messages that require adjustments or corrections, such as network settings or timeouts.
3. Network Configuration File Update:
- It is mandatory to update the network configuration file (EDS, GSDML, GSD, etc.) in the PLC software when replacing the Communicator Classic.
- To retrieve the network configuration file from the new Communicator's web interface, select the appropriate network (e.g., EtherNet/IP) and go to the Files & Firmware page.
- Click on the EDS File to download it to your computer.
- Import the downloaded network configuration file into your PLC software. The process may vary depending on the software used (e.g., Studio 5000 or TIA Portal).
- In Studio 5000, open the Hardware Installation Tool wizard in Offline mode and follow the instructions to install the EDS file.
- In TIA Portal, go to the Options menu and select Manage general station description files (GSD). Import the downloaded GSDML file into the configuration tool.
Please refer to the Anybus ABC3013 Replacing Communicator Classic with New Communicator User Guide for more detailed instructions and illustrations.