Answer

Feb 09, 2025 - 10:03 PM
Installation and setup of the Leviton ODC20-MDW Multi-Technology Ceiling-Mount Occupancy Sensor can be done following the instructions provided in the user manual. Here is a step-by-step guide:
1. Mounting: Choose a suitable location on the ceiling to mount the sensor. Ensure that it is within the recommended coverage area of 2000 square feet and at a height of 8 to 12 feet. Use the appropriate mounting hardware to secure the sensor in place.
2. Wiring: Connect the sensor to the power supply. The sensor requires a neutral wire connection. Follow the wiring diagram provided in the manual to ensure proper connection.
3. Sensor Configuration: The sensor has different configurable settings. You can choose between Manual ON/Auto OFF or Auto ON/Auto OFF modes. The time delay for turning off the lights after no motion is detected can be adjusted between 30 seconds to 30 minutes. The sensor also has a test mode for simplified commissioning.
4. Photocell Calibration: The sensor has an integrated photocell for daylight harvesting. It automatically adjusts the lighting based on the available natural light. To calibrate the photocell, cover it with a non-reflective material for 10 seconds and then uncover it. The sensor will calibrate itself to the ambient light conditions.
5. Additional Features: The sensor has several additional features, such as a walk-through feature that prevents lights from staying on for an extended period after momentary occupancy. It also has a false detection timer to prevent false triggers from HVAC systems. The sensor is designed to handle high inrush electronic ballast loads and offers short circuit protection.
For more detailed instructions and information, refer to the Leviton ODC20-MDW Multi-Technology Ceiling-Mount Occupancy Sensor User Manual.