Answer

Feb 07, 2025 - 05:14 AM
To configure the BACnet properties of the Neptronic Compact Make-up Air Unit, you need to follow these steps:
1. Set the MAC Address: The MAC address is set using the DIP switches located on the controller. Set the switches to a value between 000 and 127. Alternatively, you can set the MAC address to a value between 000 and 254 using the menu.
2. Configure the Device Instance: The device instance is automatically configured to 153,000 + MAC address. If you want to set a different device instance, you can do so manually through the menu or using the WriteProperty service to the Device Object.Object_Identifier.
3. Set the Baud Rate: The controller can automatically configure its baud rate by detecting the network upon connection. However, you can also set the baud rate manually from the available values of Auto, 9600, 19200, 38400, and 76800. This can be done through the menu or using the WriteProperty service to the Device Object.
4. Configure the Max_Master Value: The Max_Master value determines the maximum number of devices on the network. By default, it is set to 127. You can change this value through the menu or using the WriteProperty service to the Device Object.Max_Master. Adjusting this value can increase network efficiency when there are fewer than 127 devices on the network.
5. Set the Device Object Name: You can configure the name of the device through the WriteProperty service to the Device Object.Object_Name. This allows you to assign a custom name to the unit, such as "CMU".
These steps will allow you to configure the BACnet properties of the Neptronic Compact Make-up Air Unit. For more detailed information and additional configuration options, please refer to the user guide provided by Neptronic.