Answer

Feb 07, 2025 - 04:46 AM
To set the Modbus address for the Neptronic CMU-Modbus Compact Make-up Air Unit, you can use either the device menu or the holding register index. The device's unique address can be set within the range of 1 to 247.
If you prefer to use the device menu, navigate to the Modbus Address setting and enter the desired address. If you prefer to use the holding register index, write the desired address to holding register 40001.
Please refer to the Neptronic CMU-Modbus Compact Make-up Air Unit User Guide for more detailed instructions and information on setting the Modbus address and other Modbus-related settings.