Answer

Feb 03, 2025 - 07:56 PM
To configure the RS485 connection for the Janitza UMG 96-PA Power Analyzer, please follow these steps:
1. Press button 1 to open the Menu.
2. Use buttons 3 and 4 to select the menu item "Configuration" and confirm with button 6, Enter.
3. If the device is password protected, enter the password at this point.
4. The Configuration window will appear.
5. In the Configuration window, use buttons 3 and 4 to select the item "Communication" and confirm with button 6, Enter.
6. The Communication window will appear.
7. In the Communication window, configure the entries for the Fieldbus (RS485 connection), such as Device address, Baud rate, and Data frame by selecting the respective entry and confirming with button 6, Enter.
8. Use buttons 2 and 5 to change the position of the digit to be set for each item and use buttons 3 and 4 to change the digit (-1 / +1).
9. Confirm your entries with button 6, Enter, or end the action by pressing button 1, Esc.
10. To return to the standard display, press button 1 twice, Esc, and then press button 2, Home.
Please note that these instructions are based on the information provided in the Janitza UMG 96-PA Power Analyzer Instruction Manual.