Answer

Jan 29, 2025 - 03:58 AM
To apply the ALUMA-SHIELD 21059 Conductor Termination Compound to aluminum cable connections, please follow these instructions:
1. Mix the contents of the compound prior to use.
2. Coat the strands of the aluminum cable with the compound. You can brush or abrade the surfaces through the compound to ensure proper coverage. Work the compound down in between the strands.
3. Insert the coated cable into the connector and tighten or compress the joint.
4. CAUTION: Wipe off excess compound thoroughly from the outside of the connector and cable insulation.
It is important to note that the ALUMA-SHIELD 21059 Conductor Termination Compound is only UL Listed for use on electrical cables in cable connector assemblies or on bus bars rated for NEC applications up to 600 V, 1000 V in signs or fixtures, and 90ºC.
Please observe good industrial hygiene practices and wash your hands after handling the compound. Store it away from incompatible materials and dispose of waste and residues in accordance with local authority requirements.
For any further information or assistance, you can contact ABB Installation Products Inc. at the following address and emergency number:
Supplier Identification:
ABB Installation Products Inc.
860 Ridge Lake Blvd.
Memphis, Tennessee, 38120
U.S.A.
EMERGENCY NUMBER: 1-703-741-5970
Please refer to the provided website tnb.abb.com/ecpwarranty for full warranty terms.