Answer

Jan 24, 2025 - 10:00 PM
To install the STAHL 136900 Ex e Terminal Box, follow these steps:
1. Ensure that the installation location is suitable for the terminal box and complies with the specified ambient temperature range (-60 °C to +40 °C for T6, -60 °C to +55 °C for T5, and -60 °C to +70 °C for T4).
2. Make sure the enclosure is clean and free from any debris or contaminants.
3. Determine the desired entry installation options on the sides of the enclosure. The manual states that the terminal box comes without drilled holes, so you may need to drill holes according to your requirements.
4. If you need to equip the terminal box with a flange, refer to the manual for the appropriate flange size and thickness. The manual provides specific part numbers for different flange options.
5. Decide on the type of terminals you want to use. The manual mentions that the terminal box can be equipped with 1 x Phoenix UT 2-conductor terminals with a cross-section of 2.5 mm² in grey color.
6. If you require a terminal rail, the manual specifies that the terminal box comes with two 35 x 637 mm terminal rails.
7. Before mounting the terminal box, ensure that the cover screws are tightened with a torque of 4.5 Nm (39.83 lbf in).
8. Once the terminal box is securely mounted, you can proceed with connecting the necessary electrical components according to your specific application.
Please note that the information provided here is a general guideline. For detailed installation instructions and specific requirements, it is recommended to refer to the STAHL 136900 Ex e Terminal Box Instruction Manual provided by the manufacturer.