Answer
Jan 21, 2025 - 04:52 AM
To set the time on the Eltako EAW12DX-UC Analogue Settable Time Relay, follow these steps:
1. Identify the time base: The middle, latching rotary switch labeled "T" is used to select the time base. The available time base options are 0.1 seconds, 0.5 seconds, 2 seconds, 5 seconds, 1 minute, 2 minutes, 5 minutes, 1 hour, 2 hours, and 4 hours.
2. Determine the multiplier: The upper, latching rotary switch labeled "xT" is used to set the multiplier. The multiplier can be set in the range from 1 to 10.
3. Calculate the total time: Multiply the time base value selected in step 1 by the multiplier value selected in step 2. This will give you the total time setting for the relay.
4. Set the time: Use the calculated total time from step 3 to set the desired time on the Eltako EAW12DX-UC Analogue Settable Time Relay.
Note: The maximum load can be used starting at a delay time or clock cycle of 5 minutes. The maximum load will be reduced for shorter times as follows: up to 2 seconds 15%, up to 2 minutes 30%, up to 5 minutes 60%.
Please refer to the instruction manual for additional information and safety guidelines.
Add New Comment